LX3V-4DA

LX3V-4DA PLC 4 * Analog Output

Model Channels Resolution Functionality  
LX3V-4DA 4 12 bits Analog signal output

Specification

 Items LX3V-4DA
Dielectric withstand voltage 500VAC, 1min (between all terminals and ground)
Analog circuits 24V DC ± 10%, 55mA
(external power supply from main unit)
Digital circuits 5V DC, 30mA (internal power supply from main unit)
Voltage/Current Input Either voltage or current input can be selected with your choice of input terminal.
 Up to four input points can be used at one time.
Analog output range DC -10V to +10V (input resistance: 200kΩ).
Warning: this unit may be damaged by input voltage in excess of ±15V DC -20mA to +20mA (input resistance:250Ω).
Warning: this unit may be damaged by input currents in excess of ±32mA.
Digital input 12-bit conversion stored in 16-bit 2’s complement form
Maximum value: +2047 Minimum value: -2048
Resolution 5mV (10V default range 1/2000)/20µA (20mA default range 1/1000)
Over all accuracy ±1% (for the range of -10V to +10V)/±1% (for the range of -20mA to +20mA)
Conversion speed 15ms/channel (Normal speed), 6ms/channel (High speed)
CE Certification CE marked

LX3V-4DA

Références spécifiques