LX3V-2PT2DAI-B
2 * Thermal Resistance Input;
2 * Analog Output (4~20mA)
2 * Thermal Resistance Input;
2 * Analog Voltage Output(-10v-10v)
Item | LX3V-2PT2DAI-BD | LX3V-2PT2DAV-BD |
Power supply | 24VDC±10%,50mA; 5VDC±10%, 70mA (Powered by PLC host) | 5VDC±10%, 70mA (Powered by PLC host) |
Temperature input (PT) | ||
Analog input signal | PT100 sensor, 3 wires, 2 channels (CH1, CH2) | |
Sensor current | 1mA sensor: 100Ω(PT100) | |
Compensation range | -100 ℃ - 600 ℃ | |
Digital output | -1000 – 6000 (Unit: 0.1 ℃) | |
12 bits total, 11 bits for data and 1 bit for sign | ||
Accuracy | 0.2 ℃ - 0.3 ℃ | |
Overall accuracy | ±0.5% | |
Conversion rate | 50ms | |
Conversion characteristics | ||
Analog output (DAI) | Analog output (DAV) | |
Rated range | 4~20mA: 0~2000 | -10V~10V: -2000~2000 |
Analog output | DC 4~20mA (the external load resistance is no less than 500Ω) | DC-10V~10V (the external load resistance is no less than 2KΩ) |
Digital output | 12 bit binary | |
Resolution | 8uA[4~20mA / 2000] | 5mV[10V default scope 1/2000] |
Precision | ±0.5% of full scale | |
AD conversion time | One PLC scanning cycle | |
Input characteristics |
The external load is 250Ω and 0-2000 is converted to 4-20mA |
|
Insulation | No insulation in each PLC channel | |
Occupied points | None |