LX5V-2ADV-BD
2 X 12bit ANALOG VOLTAGE INPUT (-10v 10v)
Model |
Channels |
Resolution |
Functionality |
LX5V-2ADI-BD |
2 |
12 |
2*Analog Current Input (4-20mA) |
LX5V-2ADV-BD |
2 |
12 |
2*Analog Voltage Input(-10v-10v) |
LX5V-2DAI-BD |
2 |
12 |
2*Analog Current Output (4-20mA) |
LX5V-2DAV-BD |
2 |
12 |
2*Analog Voltage Output (-10v-10v) |
Specification
Item |
LX5V-2ADI-BD |
LX5V-2ADV-BD |
Current input |
Voltage input |
|
Analog input range |
DC 4mA to 20mA (input resistor 250Ω) , absolute maximum input: -2mA, +60mA |
DC-10V to 10V (input resistor 150KΩ). Note: If the input voltage exceeds ± 15V, it will be damaged. |
Digital output |
12-bit binary |
|
Resolution |
8uA (4mA to 20mA/2000) |
5mV [10V default range 1/2000] |
Comprehensive precision |
±0.5% of full scale (4mA to 20mA: ±0.16 mA) |
± 1% of full scale |
A/D conversion time |
One scan cycle (A/D conversion after ladder diagram END instruction is executed, and BD channel map value is updated) |
|
Input features |
![]() |
![]() |
Insulation |
There is no insulation between the channels of the module |
|
Points occupied |
0 point (2ADI is not affected by the standard maximum control points of the main PLC because it is operated through the data register) |
Item |
LX5V-2DAI-BD |
LX5V-2DAV-BD |
Current output |
Voltage input |
|
Analog output range |
DC 4mA to 20mA (external load resistance ≤ 500 Ω) |
DC -10V to 10V (external load resistance ≥ 500Ω) |
Digital output |
12-bit binary |
|
Resolution |
8uA (4mA to 20mA/2000) |
5mV [10V default range 1/2000] |
Comprehensive precision |
±1% of full scale (4mA to 20mA: ±0.16 mA) |
± 1% of full scale |
D/A conversion time |
One scan cycle (D/A conversion after ladder diagram END instruction is executed, and BD channel output value is updated) |
|
Output features |
External load is 250Ω. 0 to 2000 was converted to 4mA to 20mA.
|
![]() |
Insulation |
There is no insulation between the channels of the module |
|
Points occupied |
0 point (2DA is not affected by the standard maximum control points of the main PLC because it is operated through the data register) |