LX5V-2ADI2DAI-BD
2 X ANALOGUE OUTPUT 4-20mA
2 X ANALOGUE INPUT 4-20mA
Model |
Channels |
Resolution |
Functionality |
LX5V-2ADI2DAI-BD |
4 |
12 bits |
2 * Analog Input/ Analog Output (4~20mA) |
LX5V-2ADV2DAV-BD |
4 |
12 bits |
2 * Analog Input/ Output (-10V~10V) |
Specification
Item |
LX5V-2ADI2DAI-BD |
LX5V-2ADV2DAV-BD |
Power supply |
24VDC±10%, 50mA; 5VDC±10%, 70mA (The power supply is provided internally by host) |
|
ADI section |
ADV section |
|
Analog input range |
DC 4mA to 20mA (input resistor 250 Ω) absolute maximum input: -2mA, +30mA |
DC -10V to 10V (input resistor 160KΩ). ✎Note: If the input voltage exceeds ±15V, the unit will be damaged. |
Rated range |
4mA to 20mA: 0to 2000 (recommended) |
(-10V to10V: -2000 to 2000) |
Maximum display range |
-500 to 2048 |
-2048 to 2048 |
Resolution |
8uA (4mA to 20mA/2000) |
5mV (10V default range 1/2000) |
Comprehensive precision |
±0.5% of full scale (4mA to 20mA: ±0.08 mA) ±0.08 mA ) |
±0.5% of full scale |
A/D conversion time |
One scan cycle (A/D conversion after ladder diagram END instruction is executed, and BD channel mapping value is updated) |
|
Input features |
![]() |
![]() |
Insulation |
There is no insulation between the channels of the module |
|
Points occupied |
0 point (2ADI is not affected by the standard maximum control points of the main PLC because it is operated through the data register) |
|
DAI section |
DAV section |
|
Rated range |
0 to 2000: 4mA to 20mA |
DC -10V to 10V (external load resistance ≥ 2KΩ) |
Analog output range |
DC 4mA to 20mA (external load resistance ≤ 500 Ω) |
(-2000 to 2000:-10V to 10V) |
Digital output |
12-bit binary |
|
Resolution |
8uA (4mA to 20mA/2000) |
5mV (10V default range 1/2000) |
Comprehensive precision |
±0.5% of full scale (4mA to 20mA: ±0.08 mA) |
±0.5% of full scale |
D/A conversion time |
One scan cycle (D/A conversion after ladder diagram END instruction is executed, and BD channel output value is updated) |
|
Output features |
External load is 250Ω. 0 to 2000 was converted to 4mA to 20mA.
|
![]() |
Points occupied |
0 point (2DAI is not affected by the standard maximum control points of the main PLC because it is operated through the data register) |