LX5V-2PT2ADV-BD
2 X INPUT PT100 RTD
2 X ANALOGUE INPUT (-10V 10V)
Model |
Channels |
Resolution |
Functionality |
LX5V-2PT2DAI-BD |
4 |
14/12 bits |
2 * Thermal Resistance Input; 2 * Analog Output (4~20mA) |
LX5V-2PT2DAV-BD |
4 |
14/12 bits |
2 * Thermal Resistance Input; 2 * Analog Voltage Output(-10v-10v) |
Specification
Item |
LX5V-2PT2DAI-BD |
LX5V-2PT2DAV-BD |
Power supply |
24VDC±10%, 50mA; 5VDC±10%, 70mA (The power supply is provided internally by host) |
|
PT part |
||
Analog input signal |
Platinum thermal resistance PT100 sensor (100Ω), 3-wire, 2-channel input (CH1, CH2) |
|
Sensor current |
1mA sensor: 100 Ω (PT100) |
|
Compensation range |
-100 ℃ to 600 ℃ (recommended range) |
Over range display: 32767 |
Digital output |
-1000 to 6000 (unit 0.1 ℃) |
|
Measurement accuracy |
0.2℃ to 0.3℃ |
|
Total accuracy |
Full range ±0.5% (compensation range) |
|
Conversion speed |
2 channels 50ms |
|
Conversion features |
|
|
DAI section |
||
Rated range |
0 to 2000: 4mA to 20mA |
(-2000 to 2000:-10V to 10V) |
Analog output range |
DC 4mA to 20mA (external load resistance ≤ 500 Ω) |
DC -10V to 10V (external load resistance ≥ 2 K Ω) |
Digital output |
12-bit binary |
|
Resolution |
8uA (4mA to 20mA/2000) |
5mV (10V default range 1/2000) |
Comprehensive precision |
±0.5% of full scale (4mA to 20mA: ±0.08 mA) |
±0.5% of full scale |
D/A conversion time |
One scan cycle (D/A conversion after ladder diagram END instruction is executed, and BD channel output value is updated) |
|
Output features |
External load is 250Ω. 0 to 2000 was converted to 4mA to 20mA.
|
|
Points occupied |
0 point (2DAI is not affected by the standard maximum control points of the main PLC because it is operated through the data register) |