LX3V-2ADI2DAI

2 * Analog Input/ Analog Output (4~20mA)

2 * Analog Input/ Output (-10V~10V)

Item LX3V-2ADI2DAI-BD LX3V-2ADV2DAV-BD
Power supply 24VDC±10%, 50mA; 5VDC±10%, 70mA (Powered by PLC host)
Analog input (ADI) Analog input (ADV)
Analog input range DC 4~20mA (input resistance 250KΩ). Absolute maximum input: -2mA, +30mA DC-10V~10V (input resistance 160KΩ). Note: If the input voltage exceeds ±15V, the unit will be damaged.
Rated  range 4~20mA: 0~2000 -10V~10V: -2000~2000
The maximum display range -500~2048 -2048~2048
Resolution 8uA[4mA ~20mA / 2000 ] 5mV[10V default scope 1/2000]
Precision ±0.5% of full scale (4~20mA:±0.08mA) ±0.5% of full scale
AD conversion time One PLC scanning cycle
Input characteristics image.png image.png
Insulation No insulation in each PLC channel
Occupied points None
Analog output (DAI) Analog output (DAV)
Rated range 4~20mA: 0~2000 -10V~10V: -2000~2000
Analog output DC 4~20mA (the external load resistance is no less than 500Ω) DC-10V~10V (the external load resistance is no less than 2KΩ)
Digital output 12 bit binary
Resolution 8uA[4~20mA / 2000] 5mV[10V default scope 1/2000]
Precision ±0.5% of full scale
AD conversion time One PLC scanning cycle
Input characteristics

The external load is 250Ω and 0-2000 is converted to 4-20mA

image.png

image.png
Insulation No insulation in each PLC channel
Occupied points None

PLC-EXT-2ADI2DAI-BD3

Références spécifiques